WIRE REFERENCE
Wire gauge &
ampacity guide
Quick reference for common conductor sizes. Always verify the insulation, terminals, installation conditions, equipment instructions, and locally adopted code before selecting wire.
COMMON BRANCH CIRCUITS
Fast copper reference
Common maximum overcurrent protection for general copper branch-circuit conductors, subject to NEC exceptions and all applicable conditions.
75°C COLUMN
Common building-wire ampacity
For not more than three current-carrying conductors in a raceway, cable, or earth, based on a 30°C (86°F) ambient temperature. Use this column only when the conductor and every termination are permitted for 75°C.
| Wire size | Copper | Aluminum / copper-clad aluminum |
|---|---|---|
| 14 AWG | 20 A* | — |
| 12 AWG | 25 A* | 20 A* |
| 10 AWG | 35 A* | 30 A* |
| 8 AWG | 50 A | 40 A |
| 6 AWG | 65 A | 50 A |
| 4 AWG | 85 A | 65 A |
| 3 AWG | 100 A | 75 A |
| 2 AWG | 115 A | 90 A |
| 1 AWG | 130 A | 100 A |
| 1/0 AWG | 150 A | 120 A |
| 2/0 AWG | 175 A | 135 A |
| 3/0 AWG | 200 A | 155 A |
| 4/0 AWG | 230 A | 180 A |
*Small-conductor rule: Unless specifically permitted otherwise, overcurrent protection is generally limited to 15 A for 14 AWG copper, 20 A for 12 AWG copper, and 30 A for 10 AWG copper. The table ampacity is not automatically the breaker size.
BEFORE YOU SIZE IT
Six checks that can change the answer
- Load: include continuous-load and equipment-specific sizing rules.
- Terminals: use the lowest permitted temperature rating in the circuit.
- Conductors: adjust when more than three current-carrying conductors share a raceway or cable.
- Heat: correct ampacity for ambient temperature and rooftop exposure when required.
- Distance: check voltage drop; ampacity alone may not produce acceptable performance.
- Location: confirm wet/dry rating, wiring method, conductor material, and local amendments.